Feedback
iDPN Vigi, a combination of 1-pole miniature circuit breaker and earth fault protection with 2 modules’ width (36 mm), is of electromechanical type and works without external voltage sources. They are available in B- and C-curve in AC and A class as well as in Asi design, i.e. short-time delayed with elevated power surge resistance and breaking capacity 6kA or respectively 10kA. iDPN Vigi can be supplied with help functions for indication (help/signal contact) and remote tripping (shunt/undervoltage trigger), the same accessories as inC60 are used in addition to OF and SD, where A9A26924 (OF) and A9A26927 (SD) are to be used. Since the device has two connections with 9 mm space, there are special phase rails for this series (21505,21507,21093). Connections: tunnel connections up to 10 mm².
- Article number: 2164985
- Suppl. article no: A9D31610
- Ean no: 3606480471988
- Replaces art.nbr: 2165207
- Material class QL5400
Technical data
- Packagin Size: 1 ST/6 ST/54 ST
- Type: A9D31610
- Product series: Acti 9
- Number of poles (total): 2
- Number of protected poles: 1
- Rated current: 10 A
- Rated fault current: 0.03 A
- Rated short-circuit breaking capacity according to IEC 60947-2: 6 kA
- Release characteristic: C
- Leakage current type: AC
- Rated voltage: 230 V
- Frequency: 50 Hz
- Voltage type: AC
- Width in number of modular spacings: 2
- Rated short-circuit breaking capacity according to EN 61009: 6 kA
- Rated short-circuit breaking capacity Icn according to EN 61009-1: 6 kA
- Current limiting class: 3
- Anti-nuisance tripping version: No
- Degree of protection (IP): IP20
- Overvoltage category: 3
- Concurrently switching neutral conductor: Yes
- Pollution degree: 3
- Surge current capacity: 0.25 kA
- Ambient temperature during operating: -5-60 °C
- Rated impulse withstand voltage Uimp: 4 kV
- Rated insulation voltage Ui: 400 V
- With interlocking device: Yes
- Disconnection characteristic: Other
- Connectable conductor cross section solid-core: 1-16 mm²
- Connectable conductor cross section multi-wired: 1-10 mm²
- Flush-mounted installation: No
- Power loss: 2.9 W
- Built-in depth: 44 mm
- Mounting method: DIN rail
- REACH Date: 2025-07-18
- REACH contains candidate substances: Bly
- REACH Information obligation: Yes