Feedback
Halogen-free flame-retardant signal cable. EQQRB is used as a signal cable in various control and regulation technical systems, including fire alarm systems. It can be placed indoors or outdoors. Meets fire requirements according to CPR class Dcas2d2a2.
- Article number: 4836850
- Suppl. article no: 18440271-802-00
- Ean no: 7330000098015
- Material class QR0600
Technical data
- Cable type: EQQRB
- Dimension conductor x diameter: 2x1 mm
- Diameter conductor: 1 mm
- Reaction-to-fire according to EN 13501-6: Class: Dca
- Cable geometry: Flat
- Outer diameter approximate: 4.9 mm
- Colour outer sheath: White
- Halogen free according to EN IEC 60754-2: Yes
- Conductor material: Copper
- Specification material outer sheath: Other
- Core identification according to HD 308 S2: Yes
- Longitudinal water blocking cable: No
- Radial water blocking cable: No
- Screen over stranding element: None
- Screen over stranding: None
- Conductor category: Class 1 = solid
- Material outer sheath: Polyolefin
- Core identification: Colour
- Stranding element: No
- Material core insulation: Polyolefin
- Stranding: Layers
- Permitted cable outer temperature after assembling without vibration: -40-70 °C
- Permitted cable outer temperature during assembling/handling: -10-50 °C
- Reaction-to-fire according to EN 13501-6: Flaming droplets/particles: d2
- Conductor surface: Bare
- Suitable for underground installation: Yes
- Min. permitted bending radius, stationary application/permanent installation: 40 mm
- Oil resistant according to EN IEC 60811-404: No
- Low smoke according to EN IEC 61034-2: Yes
- Reaction-to-fire according to EN 13501-6: Smoke production: s2
- Specification core insulation: Other
- Reaction-to-fire according to EN 13501-6: Acidity: a2
- UV resistant: No
- Certified for shipboard application: No
- Suitable as computer data cable: No
- Suitable as signalling cable: Yes
- Suitable as telephone cable: No
- Approved type of underground installation: Underground installation tube
- Weight: 27 kg/km
- Insulation integrity according to IEC 60331: No
- Number of cores: 2
- REACH Date: 2021-06-14
- GWP-tot (A1-A3): 0,0771 kgCO2e/M
- REACH Information obligation: No