Feedback
HFFR-insulated signal cable with halogen-free, fl shielded sheath. Conductor of single-wire copper. It is an HFFR-insulated signal cable with a halogen-free, fl-shielded sheath. EQQRB is used as a signal cable in various control and regulation technical systems, including fire alarm systems. The cable is designed according to SS 424 16 09. Placed indoors according to SS 424 14 38 and outdoors, also on a carrying line and protected against mechanical damage in the ground according to SS 424 14 37. Meets fire requirements according to CPR class Dcas2d2a2. In the event of a fire, the cable emits no corrosive gases and has little smoke evolution.
- Article number: 4836890
- Suppl. article no: 18440271-803-00
- Ean no: 7330000113459
- Material class QR0600
Technical data
- Cable type: EQQRB
- Dimension conductor x diameter: 2x1 mm
- Reaction-to-fire according to EN 13501-6: Class: Dca
- Outer diameter approximate: 4.9 mm
- Screen over stranding element: None
- Screen over stranding: None
- Colour outer sheath: Red
- Low smoke according to EN IEC 61034-2: Yes
- Halogen free according to EN IEC 60754-2: Yes
- Reaction-to-fire according to EN 13501-6: Acidity: a2
- Material core insulation: Polyolefin
- Conductor category: Class 1 = solid
- Conductor material: Copper
- Core identification: Colour
- Specification core insulation: Other
- Diameter conductor: 1 mm
- Core identification according to HD 308 S2: Yes
- Conductor surface: Bare
- Number of cores: 2
- Cable geometry: Flat
- Stranding: Layers
- Permitted cable outer temperature after assembling without vibration: -40-70 °C
- Suitable for underground installation: Yes
- Approved type of underground installation: Underground installation tube
- Weight: 27 kg/km
- Reaction-to-fire according to EN 13501-6: Flaming droplets/particles: d2
- Stranding element: No
- Min. permitted bending radius, stationary application/permanent installation: 40 mm
- Longitudinal water blocking cable: No
- Radial water blocking cable: No
- Permitted cable outer temperature during assembling/handling: -10-50 °C
- Reaction-to-fire according to EN 13501-6: Smoke production: s2
- Certified for shipboard application: No
- Suitable as computer data cable: No
- Suitable as telephone cable: No
- Suitable as signalling cable: Yes
- Material outer sheath: Polyolefin
- Specification material outer sheath: Other
- UV resistant: No
- Oil resistant according to EN IEC 60811-404: No
- REACH Date: 2021-06-14
- GWP-tot (A1-A3): 0,0771 kgCO2e/M
- REACH Information obligation: No