Feedback

Rutab
Installation cable, shielded, fire-resistant Novosafe 300/500 V, Rutab
S(ST)-FE-180/PH90 2X1.0 (*5)
Article number: Suppl. article no:
0477080
0477080
to see price and stock
Fire-resistant halogen-free installation and fire alarm cable in shielded design. Intended for permanent installation in buildings for the public such as schools, hospital shops, etc. Suitable for use in fire alarm systems, control systems and in other installations where high demands are made on fire safety. its electrical function for at least 90 minutes (PH90) Complies with fire spreading class IEC 60332-3-22 (F4A) Halogen-free IEC 60754-2 Flameproof IEC 60332-1 Low smoke generation IEC 61034-2, Fireproof IEC 60331-11, -21 , -23, PH 90 (90 min, 830 ° C) Color: Red
Cable type: Novosafe S (St) -FE-180 / PH90
Operating voltage: 300/500 V
Conductor structure: One-piece shiny copper at 1 p.m.
Conductor insulation: Ceramic silicone rubber
Shade: Aluminum / polyester foil with tinned image guide
Outer sheath: Halogen-free special mixture, Red
Temperature range: -40 ° C - + 80 ° C
Minimum placement temperature: -10 ° C
Fire spread class: IEC 60332-3-22 (F4A)
Cable type: Novosafe S (St) -FE-180 / PH90
Operating voltage: 300/500 V
Conductor structure: One-piece shiny copper at 1 p.m.
Conductor insulation: Ceramic silicone rubber
Shade: Aluminum / polyester foil with tinned image guide
Outer sheath: Halogen-free special mixture, Red
Temperature range: -40 ° C - + 80 ° C
Minimum placement temperature: -10 ° C
Fire spread class: IEC 60332-3-22 (F4A)
- Article number: 0477080
- Suppl. article no: 0477080
- Material class QA820B
Technical data
- Cable type: NOVOSAFE S(ST)-FE
- Dimension conductor x area: 2x1 mm²
- Outer diameter approximate: 7.1 mm
- Nominal voltage U0: 300 V
- Nominal voltage U: 500 V
- With protective conductor: No
- Colour outer sheath: Red
- Conductor category: Class 1 = solid
- Conductor material: Copper
- Shape of conductor: Round
- Max. permitted conductor temperature: 90 °C
- Low smoke according to EN IEC 61034-2: Yes
- Halogen free according to EN IEC 60754-2: Yes
- Screen: Yes
- Material core insulation: Other
- Core identification: Colour
- Specification core insulation: Rubber - silicone rubber (SIR)
- Core identification according to HD 308 S2: Yes
- Nominal cross section conductor: 1 mm²
- Conductor surface: Bare
- Number of cores: 2
- Cable geometry: Round
- Permitted cable outer temperature after assembling without vibration: -40-80 °C
- Drain wire: Yes
- Weight: 63 kg/km
- Flame retardant according to IEC 60332-3-22 (Cat A): Yes
- Circuit integrity according to DIN 4102-12: E90
- Circuit integrity according to EN 50200: 90 min
- Circuit integrity according to IEC 60331-1: 90 min
- Circuit integrity according to IEC 60331-2: 90 min
- Circuit integrity according to IEC 60331-3: 90 min
- Suitable as installation cable: Yes
- Material outer sheath: Polyolefin
- REACH Date: 2021-11-24
- REACH Information obligation: No