Feedback
EQLQ is a HFFR-insulated, aluminium shielded and HFFR-sheathed installation cable with round, solid copper conductor. The cable is designed in accordance with SS 424 02 19-2 as applicable. The line has a wire count and resistance in accordance with IEC 60228 class 1. The parts are colour marked according to SS 424 17 20. The cable has an extruded filler. The sheathe is labelled NEXANS GS Ds2d2a2. EQRQ meets fire requirements according to CPR class Dcas2d2a2. Conductor insulation must be protected against direct UV light which may occur, for example, in the lighting luminaires and light signs.
Lifemark(TM) recycling marking. Resistant outer marking on the cable’s outer sheath. The marking specifies included plastic grades and preparation for future recycling of the cable.
Certified in accoardance with ISO 9001, IRIS, ISO/TS 16949 and ISO 14001.
Lifemark(TM) recycling marking. Resistant outer marking on the cable’s outer sheath. The marking specifies included plastic grades and preparation for future recycling of the cable.
Certified in accoardance with ISO 9001, IRIS, ISO/TS 16949 and ISO 14001.
- Article number: 0443001
- Suppl. article no: 14100130-802-01
- Ean no: 7330000080959
- Material class QA6550
Technical data
- Packagin Size: 50 M/1800 M
- Cable type: EQRQ
- Dimension conductor x area: 3G1,5 mm²
- Reaction-to-fire according to EN 13501-6: Class: Dca
- Outer diameter approximate: 7.1 mm
- Nominal voltage U0: 300 V
- Nominal voltage U: 500 V
- With protective conductor: Yes
- Colour outer sheath: White
- Conductor category: Class 1 = solid
- Conductor material: Copper
- Shape of conductor: Round
- Max. permitted conductor temperature: 70 °C
- Low smoke according to EN IEC 61034-2: Yes
- Armouring/reinforcement: None
- Halogen free according to EN IEC 60754-2: Yes
- Reaction-to-fire according to EN 13501-6: Acidity: a2
- Screen: Yes
- Material core insulation: Polyolefin
- Conductor resistance at 20 °C: 12.1 Ohm/km
- Core identification: Colour
- Core identification according to HD 308 S2: Yes
- Nominal cross section conductor: 1.5 mm²
- Conductor surface: Bare
- Number of cores: 3
- Cable geometry: Round
- Permitted cable outer temperature after assembling without vibration: -40-70 °C
- Drain wire: No
- Suitable for underground installation: No
- Weight: 108 kg/km
- Weight/100 m: 10 kg
- Low temperature resistant according to EN 60811-504+505+506: Yes
- Reaction-to-fire according to EN 13501-6: Flaming droplets/particles: d2
- Permitted cable outer temperature during assembling/handling: -10-50 °C
- Reaction-to-fire according to EN 13501-6: Smoke production: s2
- Suitable as installation cable: Yes
- Protective barrier: Al/PE
- Material outer sheath: Polyolefin
- Oil resistant according to EN IEC 60811-404: No
- REACH Date: 2021-06-14
- GWP-tot (A1-A3): 0,3129 kgCO2e/M
- REACH Information obligation: No