Feedback

Connection cable RQ (H07Z1-K) 450/750V ≥4.0mm² Dca - RQ 120 450/750V BLACK (*0)
Nexans

Connection cable RQ (H07Z1-K) 450/750V ≥4.0mm² Dca

RQ 120 450/750V BLACK (*0)
Article number: 
0369510
Suppl. article no: 
11196298-801-00





 to see price and stock
Third party verified Environmental product declarationProdukten är bedömd hos Byggvarubedömningen med totalbedömningen Accepteras.
The cable is primarily intended to be used for internal connections in junction cabinets or the like. RQ is a halogen-free, HFFR-insulated, coupling line with a round multi-stranded copper conductor. The cable is constructed according to SS 424 02 31-3 in applicable parts. The conductor has resistance according to IEC 60228 class 5. The insulation is marked "NEXANS GS Z1 SEMKO AREA mm2" or "NEXANS GS SEMKO area mm² HALOGEN FREE". RQ meets fire spread class D. The cable is approved by SEMKO.
  • Article number: 
    0369510
  • Suppl. article no: 
    11196298-801-00
  • Ean no: 
    7330000083714
  • Material class 
    QA4800
Technical data
  • Cable type: RQ
  • Dimension conductor x area: 120 mm²
  • Core colour: Black
  • Reaction-to-fire according to EN 13501-6: Class: Dca
  • Diameter conductor: 19 mm
  • Outer diameter approximate: 17.9 mm
  • Screen: No
  • Permitted cable outer temperature during assembling/handling: -10-50 °C
  • Low temperature resistant according to EN 60811-504+505+506: Yes
  • Permitted cable outer temperature after assembling without vibration: -40-70 °C
  • Conductor category: Class 5 = flexible
  • Nominal voltage U0: 450 V
  • Nominal voltage U: 750 V
  • Material core insulation: Polyolefin
  • Armouring/reinforcement: None
  • Drain wire: No
  • Reaction-to-fire according to EN 13501-6: Flaming droplets/particles: d2
  • Conductor material: Copper
  • Conductor surface: Bare
  • Max. permitted conductor temperature: 70 °C
  • Min. permitted bending radius, stationary application/permanent installation: 71.6 mm
  • Core identification: Colour
  • Reaction-to-fire according to EN 13501-6: Smoke production: s2
  • Protective barrier: None
  • Reaction-to-fire according to EN 13501-6: Acidity: a2
  • Certified for shipboard application: No
  • Certified as airport lighting cable: No
  • Cable geometry: Round
  • Shape of conductor: Round
  • Conductor resistance at 20 °C: 0.161 Ohm/km
  • Suitable as installation cable: Yes
  • Core identification according to HD 308 S2: Yes
  • Weight: 1087 kg/km
  • Number of cores: 1
  • Nominal cross section conductor: 120 mm²
  • REACH Date: 2021-06-14
  • GWP-tot (A1-A3): 2,9317 kgCO2e/M
  • REACH Information obligation: No