Feedback
The cable is primarily intended to be used for fixed protected installation of signal and control circuits in appliances. RQ is a halogen-free, HFFR-insulated, coupling line with a round multi-stranded copper conductor. The cable is constructed in accordance with SS 424 02 31-3 in applicable parts. The conductor has resistance according to IEC 60228 class 5. The insulation is marked "NEXANS GS Z1 SEMKO area mm²". RQ meets fire spread class D. The cable is approved by SEMKO.
- Article number: 0344633
- Suppl. article no: 11194246-807-21
- Ean no: 7330000084254
- Replaces art.nbr: 0351043
- Material class QA4650
Technical data
- Packagin Size: 56000 M
- Cable type: RQ
- Dimension conductor x area: 0.75 mm²
- Core colour: Grey
- Reaction-to-fire according to EN 13501-6: Class: Dca
- Outer diameter approximate: 2.3 mm
- Nominal voltage U0: 300 V
- Nominal voltage U: 500 V
- Conductor category: Class 5 = flexible
- Conductor material: Copper
- Diameter conductor: 3 mm
- Shape of conductor: Round
- Max. permitted conductor temperature: 70 °C
- Low smoke according to EN IEC 61034-2: Yes
- Armouring/reinforcement: None
- Halogen free according to EN IEC 60754-1: Yes
- Halogen free according to EN IEC 60754-2: Yes
- Reaction-to-fire according to EN 13501-6: Acidity: a2
- Screen: No
- Material core insulation: Polyolefin
- Core identification: Colour
- Nominal cross section conductor: 0.75 mm²
- Conductor surface: Bare
- Number of cores: 1
- Cable geometry: Round
- Permitted cable outer temperature after assembling without vibration: -40-70 °C
- Drain wire: No
- Weight: 11 kg/km
- Weight/100 m: 1.2 kg
- Low temperature resistant according to EN 60811-504+505+506: No
- Reaction-to-fire according to EN 13501-6: Flaming droplets/particles: d2
- Circuit integrity according to BS 6387 CWZ: No
- Circuit integrity according to BS 8434-2: No
- Circuit integrity according to BS 8491: No
- Reaction-to-fire according to EN 13501-6: Smoke production: s2
- Certified for shipboard application: No
- Certified as airport lighting cable: No
- Suitable as installation cable: Yes
- Protective barrier: None
- Oil resistant according to EN IEC 60811-404: No
- REACH Date: 2021-06-14
- GWP-tot (A1-A3): 0,0205 kgCO2e/M
- REACH Information obligation: No