NKT
Control cable halogen-free FQAR-PG 150/250 V, Nkt
FQAR-PG 4X2X1 1CCC K
Article number:
0174000
to see price and stock
Halogen-free cable that in case of fire gives off a smoke that is free from corrosive gases and has a low density. For fixed installations indoors and outdoors, open and in pipes and ducts. For signalling where high demands on immunity from disturbances and protection against overheating.
Stranded, tempered tinned copper according to IEC 60228, class 2, SS4241475 (F3). Halogen-free numbered insulation. Parties twined in pairs before cabling and bound with PET foil.
Screen: Plastic laminated aluminium foil with bi-conductor.
Sleeve marking, example: “nkt cables FQAR-PG 4x2x0,5 150/250 V"
Certificates: Standard SS 424 03 21, HD 627 Part 4 C2 itd
Operating temperature: Maximum 70°C during continuous operation.
Stranded, tempered tinned copper according to IEC 60228, class 2, SS4241475 (F3). Halogen-free numbered insulation. Parties twined in pairs before cabling and bound with PET foil.
Screen: Plastic laminated aluminium foil with bi-conductor.
Sleeve marking, example: “nkt cables FQAR-PG 4x2x0,5 150/250 V"
Certificates: Standard SS 424 03 21, HD 627 Part 4 C2 itd
Operating temperature: Maximum 70°C during continuous operation.
- Article number: 0174000
- Ean no: 5702950291556
- Material class QA3100
Technical data
- Cable type: FQAR-PG
- Dimension conductor x area: 4x2x1 mm²
- With protective conductor: No
- Screen over stranding element: None
- Screen over stranding: Foil
- Outer diameter approximate: 12 mm
- Weight/100 m: 16.0 kg
- Conductor category: Class 2 = stranded
- Colour outer sheath: Grey
- Material outer sheath: Polyolefin
- Material core insulation: Polyolefin
- Nominal voltage U: 250 V
- Core identification: Numbers
- Stranding element: Pairs
- Flame retardant according to IEC 60332-1-2: Yes
- Halogen free according to EN IEC 60754-1: Yes
- Halogen free according to EN IEC 60754-2: Yes
- Low smoke according to EN IEC 61034-2: Yes
- Number of cores: 8
- Nominal cross section conductor: 1 mm²
- REACH Date: 2021-12-09
- REACH Information obligation: No