Feedback
AhlsellProductsElectricCable 00-05, 48-4901 Control cable, single core and strandedControl cable halogen-free

NKT
Control cable halogen-free FQAR-PG 150/250 V, Nkt
FQAR-PG 2X2X0.5 D500 (*0)
Article number:
0173915
to see price and stock
Halogen-free cable that in case of fire gives off a smoke that is free from corrosive gases and has a low density. For fixed installations indoors and outdoors, open and in pipes and ducts. For signalling where high demands on immunity from disturbances and protection against overheating.
Stranded, tempered tinned copper according to IEC 60228, class 2, SS4241475 (F3). Halogen-free numbered insulation. Parties twined in pairs before cabling and bound with PET foil.
Screen: Plastic laminated aluminium foil with bi-conductor.
Sleeve marking, example: “nkt cables FQAR-PG 4x2x0,5 150/250 V"
Certificates: Standard SS 424 03 21, HD 627 Part 4 C2 itd
Operating temperature: Maximum 70°C during continuous operation.
Stranded, tempered tinned copper according to IEC 60228, class 2, SS4241475 (F3). Halogen-free numbered insulation. Parties twined in pairs before cabling and bound with PET foil.
Screen: Plastic laminated aluminium foil with bi-conductor.
Sleeve marking, example: “nkt cables FQAR-PG 4x2x0,5 150/250 V"
Certificates: Standard SS 424 03 21, HD 627 Part 4 C2 itd
Operating temperature: Maximum 70°C during continuous operation.
- Article number: 0173915
- Ean no: 5702950269166
- Material class QA3150
Technical data
- Packagin Size: 500 M
- Cable type: FQAR-PG
- Dimension conductor x area: 2x2x0.50 mm²
- Outer diameter approximate: 7 mm
- Nominal voltage U: 250 V
- With protective conductor: No
- Colour outer sheath: Grey
- Conductor category: Class 2 = stranded
- Low smoke according to EN IEC 61034-2: Yes
- Halogen free according to EN IEC 60754-2: Yes
- Halogen free according to EN IEC 60754-1: Yes
- Material core insulation: Polyolefin
- Core identification: Numbers
- Nominal cross section conductor: 0.5 mm²
- Number of cores: 4
- Weight/100 m: 7.3 kg
- Flame retardant according to IEC 60332-1-2: Yes
- Stranding element: Pairs
- Screen over stranding element: None
- Material outer sheath: Polyolefin
- Screen over stranding: Foil
- REACH Date: 2021-12-09
- REACH Information obligation: No