NKT
Control cable EQLR 300/500V Dca, Nkt
EQLR 7X1.5 DCA (*5)
Article number:
0157660
to see price and stock
Halogen-free cable, which in case of fire emits smoke free from corrosive gases and with low smoke density. For fixed installation indoors and outdoors, also suspended on the carrier line and in soil or water. The cable is well suited for installations where external electrical interference is feared.
Threaded conductor, annealed copper according to IEC 60228, class 1. Halogen-free insulation, digit marked.
Filling: Banding and halogen-free sprayed layer
Supervisor: Tinned copper
Shade / Inner jacket: Aluminum with adhesive polyethylene
Mantle: Halogen free, gray
Sheath marking: Meter marked, example: "nkt cables EQLR 300/500 V"
Approval: CE
Construction standard: SS 424 03 21, HD 627 Part 4 C1 where applicable.
Fire Class: DcaS2d2
Operating temperature: Max 70ºC for continuous operation
Threaded conductor, annealed copper according to IEC 60228, class 1. Halogen-free insulation, digit marked.
Filling: Banding and halogen-free sprayed layer
Supervisor: Tinned copper
Shade / Inner jacket: Aluminum with adhesive polyethylene
Mantle: Halogen free, gray
Sheath marking: Meter marked, example: "nkt cables EQLR 300/500 V"
Approval: CE
Construction standard: SS 424 03 21, HD 627 Part 4 C1 where applicable.
Fire Class: DcaS2d2
Operating temperature: Max 70ºC for continuous operation
- Article number: 0157660
- Ean no: 7394479011869
- Material class QA3200
Technical data
- Cable type: EQLR
- Dimension conductor x area: 7x1.5 mm²
- Reaction-to-fire according to EN 13501-6: Class: Dca
- Outer diameter approximate: 12 mm
- Nominal voltage U: 500 V
- Screen over stranding element: None
- Screen over stranding: Foil
- Colour outer sheath: Grey
- Reaction-to-fire according to EN 13501-6: Acidity: a2
- Material core insulation: Polyolefin
- Conductor category: Class 1 = solid
- Conductor material: Copper
- Core identification: Numbers
- Nominal cross section conductor: 1.5 mm²
- Conductor surface: Bare
- Number of cores: 7
- Cable geometry: Round
- Weight/100 m: 25.5 kg
- Reaction-to-fire according to EN 13501-6: Flaming droplets/particles: d2
- Stranding element: No
- Reaction-to-fire according to EN 13501-6: Smoke production: s2
- Material outer sheath: Polyolefin
- Oil resistant according to EN IEC 60811-404: No
- REACH Date: 2021-12-09
- REACH Information obligation: No