Feedback

Control cable EQFR (S07XC7Z1-U) 450/700V Dca, Nexans - EQFR 7X1.5 500V LGREY 750 K
Nexans

Control cable EQFR (S07XC7Z1-U) 450/700V Dca, Nexans

EQFR 7X1.5 500V LGREY 750 K
Article number: 
0127610
Suppl. article no: 
16174198-898-00





 to see price and stock
Produkten är bedömd hos Byggvarubedömningen med totalbedömningen Accepteras.
The cable is intended for fixed installation indoors and outdoors, even in ground and water, for control, measuring and signaling functions in power engineering plants.
EQFR is a halogen-free, PEX-insulated, copper-wire shielded and HFFR-coated control cable with round, solid copper conductors. The cable is designed according to SS 424 03 21 in applicable parts. The conductors have thread count and resistance according to IEC 60228 class 1. The parties are number marked according to SS 424 17 20. The jacket is marked type / manufacturer / year + month / meter marking. EQFR complies with fire spread class D and emits no corrosive gases in the event of fire and has little smoke emission. The cable is approved by SEMKO.
The cable is marked with Lifemark TM recycling mark (content declared).
  • Article number: 
    0127610
  • Suppl. article no: 
    16174198-898-00
  • Ean no: 
    7330000075733
  • Replaces art.nbr: 
    0153020
  • Material class 
    QA3001
Technical data
  • Cable type: EQFR
  • Dimension conductor x area: 7x1.5 mm²
  • Reaction-to-fire according to EN 13501-6: Class: Dca
  • Outer diameter approximate: 13 mm
  • Nominal voltage U0: 450 V
  • Nominal voltage U: 750 V
  • With protective conductor: Yes
  • Colour outer sheath: Grey
  • Conductor category: Class 1 = solid
  • Conductor material: Copper
  • Max. permitted conductor temperature: 70 °C
  • Low smoke according to EN IEC 61034-2: Yes
  • Halogen free according to EN IEC 60754-2: Yes
  • Reaction-to-fire according to EN 13501-6: Acidity: a2
  • Material core insulation: Polyolefin
  • Conductor resistance at 20 °C: 12.1 Ohm/km
  • Core identification: Numbers
  • Core identification according to HD 308 S2: Yes
  • Shape of conductor: Round
  • Nominal cross section conductor: 1.5 mm²
  • Conductor surface: Bare
  • Number of cores: 7
  • Cable geometry: Round
  • Screen: Yes
  • Permitted cable outer temperature after assembling without vibration: -40-70 °C
  • Drain wire: No
  • Weight: 266 kg/km
  • Weight/100 m: 29 kg
  • Low temperature resistant according to EN 60811-504+505+506: Yes
  • Reaction-to-fire according to EN 13501-6: Flaming droplets/particles: d2
  • Stranding element: No
  • Min. permitted bending radius, stationary application/permanent installation: 104 mm
  • Min. permitted bending radius, moving application with forced guidance: 104 mm
  • Permitted cable outer temperature during assembling/handling: -10-50 °C
  • Reaction-to-fire according to EN 13501-6: Smoke production: s2
  • Material outer sheath: Polyolefin
  • Screen over stranding: None
  • REACH Date: 2021-06-14
  • With rodent protection: No
  • Core colour: White
  • REACH Information obligation: No
  • Suitable for underground installation: Yes
  • Radial water blocking cable: No