Feedback
The cable is intended for fixed installation indoors and outdoors in air, ground and water. The cable is intended for fixed installation indoors and outdoors in air, ground and water. FXQ Easy ™ is a PEX-insulated, HFFR-coated installation cable with a copper wired conductor. The cable is designed according to SS 424 14 18 ITD. The conductor has thread count and resistance according to IEC 60228 class 2. The cable has an inner layer on the sheath which is grooved. The grooves make the cable extremely easy-peeled and resistant to impact and pressure. The mantle is labeled type / manufacturer / year + month / meter marking. FXQ Easy ™ meets fire spread class D and is UV protected according to HD626 S1 part 2.5.1. The conductor insulation must be protected against direct UV light that may occur, for example, in lighting fixtures and light signs. The cable is marked with Lifemark TM recycling mark (content declared).
- Article number: 0054375
- Suppl. article no: 15101298-201-05
- Ean no: 7330000079458
- Replaces art.nbr: 0013375
- Material class QA0350
Technical data
- Packagin Size: 500 M
- Cable type: FXQ Easy
- Dimension conductor x area: 4G6 mm²
- Outer diameter approximate: 16 mm
- Reaction-to-fire according to EN 13501-6: Class: Dca
- Colour outer sheath: Black
- Weight: 376 kg/km
- Weight/100 m: 43 kg
- Nominal voltage U: 1 kV
- Nominal voltage U0: 0.6 kV
- Conductor category: Class 2 = stranded
- Conductor material: Copper
- Halogen free according to EN IEC 60754-2: Yes
- Reaction-to-fire according to EN 13501-6: Smoke production: s2
- Reaction-to-fire according to EN 13501-6: Flaming droplets/particles: d2
- Reaction-to-fire according to EN 13501-6: Acidity: a2
- Shape of conductor: Round
- Screen: No
- Drain wire: No
- Lead sheath: No
- Permitted cable outer temperature after assembling without vibration: -40-70 °C
- Permitted cable outer temperature during assembling/handling: -10-50 °C
- Concentric conductor: None
- Material outer sheath: Polyolefin
- Core identification: Colour
- With protective conductor: Yes
- Material core insulation: Other
- Max. permitted conductor temperature: 90 °C
- Fibre optic elements: No
- Inner semi-conducting layer: No
- Laminated sheath: No
- Conductive coating: No
- Conductor surface: Bare
- Longitudinal water blocking conductors: No
- Low smoke according to EN IEC 61034-2: Yes
- Outer semi-conducting layer: No
- Certified for shipboard application: No
- Certified as airport lighting cable: No
- Cable geometry: Round
- Suitable as installation cable: Yes
- Min. permitted bending radius, stationary application/permanent installation: 128 mm
- Core identification according to HD 308 S2: Yes
- Conductor resistance at 20 °C: 3.08 Ohm/km
- Specification core insulation: Crosslinked polyethylene (XLPE)
- Diameter conductor: 3 mm
- Suitable for underground installation: Yes
- Max. tensile strength during installation: 1.2 kN
- Oil resistant according to EN IEC 60811-404: No
- Number of cores: 4
- UV resistant: Yes
- Nominal cross section conductor: 6 mm²
- REACH Date: 2021-06-14
- GWP-tot (A1-A3): 1,0979 kgCO2e/M
- REACH Information obligation: No