Feedback

New in the online store
Nexans
MXQ EASY 5G6 1kV Black R30
MXQ EASY™ 5G6 1KV BLACK R30
Article number: Suppl. article no:
0017353
15066130-201-30
to see price and stock
MXQ Easy™ is a halogen-free, PEX-insulated, unshielded and HFFR-sheathed cable with round stranded copper conductors.
- Article number: 0017353
- Suppl. article no: 15066130-201-30
- Material class QA0352
Technical data
- Packagin Size: 30 M/180 M/720 M
- Outer diameter approximate: 17 mm
- Reaction-to-fire according to EN 13501-6: Class: Dca
- Colour outer sheath: Black
- Weight: 453 kg/km
- Nominal voltage U: 1 kV
- Nominal voltage U0: 0.6 kV
- Conductor category: Class 2 = stranded
- Conductor material: Copper
- Halogen free according to EN IEC 60754-2: Yes
- Reaction-to-fire according to EN 13501-6: Smoke production: s2
- Reaction-to-fire according to EN 13501-6: Flaming droplets/particles: d2
- Reaction-to-fire according to EN 13501-6: Acidity: a2
- Shape of conductor: Round
- Screen: No
- Drain wire: No
- Lead sheath: No
- Permitted cable outer temperature after assembling without vibration: -40-70 °C
- Permitted cable outer temperature during assembling/handling: -10-50 °C
- Concentric conductor: None
- Material outer sheath: Polyolefin
- Core identification: Colour
- With protective conductor: Yes
- Material core insulation: Other
- Max. permitted conductor temperature: 90 °C
- Fibre optic elements: No
- Inner semi-conducting layer: No
- Laminated sheath: No
- Conductive coating: No
- Conductor surface: Bare
- Longitudinal water blocking conductors: No
- Low smoke according to EN IEC 61034-2: Yes
- Outer semi-conducting layer: No
- Certified for shipboard application: No
- Certified as airport lighting cable: No
- Cable geometry: Round
- Suitable as installation cable: Yes
- Min. permitted bending radius, stationary application/permanent installation: 136 mm
- Core identification according to HD 308 S2: Yes
- Conductor resistance at 20 °C: 3.08 Ohm/km
- Specification core insulation: Crosslinked polyethylene (XLPE)
- Diameter conductor: 3 mm
- Suitable for underground installation: Yes
- Max. tensile strength during installation: 1.5 kN
- Oil resistant according to EN IEC 60811-404: No
- Number of cores: 5
- Nominal cross section conductor: 6 mm²
- REACH Date: 2026-01-13
- REACH Information obligation: No