Axclight TT is a longitudinally and transversely waterproof, halogen-free, PEX-insulated, CU-shielded medium voltage cable.
- Article number: 0072915
- Suppl. article no: 21230398-201-05
- Material class QA2450
Technical data
- Packagin Size: 500 M
- Cable type: Axclight-TT
- Dimension conductor x area: 3x95/25 mm²
- Reaction-to-fire according to EN 13501-6: Class: None
- Outer diameter approximate: 47 mm
- Nominal voltage U0: 7 kV
- Nominal voltage U: 12 kV
- Colour outer sheath: Black
- Conductor category: Class 2 = stranded
- Conductor material: Aluminium
- Max. permitted conductor temperature: 90 °C
- Halogen free according to EN IEC 60754-2: Yes
- Reaction-to-fire according to EN 13501-6: Acidity: None
- Conductor resistance at 20 °C: 0.32 Ohm/km
- Core identification: None
- Conductive coating: No
- Specification core insulation: Crosslinked polyethylene (XLPE)
- Core identification according to HD 308 S2: No
- Shape of conductor: Round
- Nominal cross section conductor: 95 mm²
- Conductor surface: Bare
- Number of cores: 3
- Cable geometry: Round
- Concentric conductor: Copper
- Nominal cross section concentric conductor: 25 mm²
- Screen: Yes
- Longitudinal water blocking screen: Yes
- Permitted cable outer temperature after assembling without vibration: -40-70 °C
- Laminated sheath: Yes
- Lead sheath: No
- Suitable for underground installation: Yes
- Max. tensile strength during installation: 8.6 kN
- Weight: 2155 kg/km
- Reaction-to-fire according to EN 13501-6: Flaming droplets/particles: None
- Min. permitted bending radius, stationary application/permanent installation: 470 mm
- Longitudinal water blocking conductors: Yes
- Radial water blocking cable: Yes
- Permitted cable outer temperature during assembling/handling: -20-50 °C
- Reaction-to-fire according to EN 13501-6: Smoke production: None
- Inner semi-conducting layer: Yes
- Suitable as medium-voltage cable: Yes
- Protective barrier: Al/PE
- Material outer sheath: Other
- Specification material outer sheath: Polyethylene (PE)
- Outer semi-conducting layer: Yes
- UV resistant: Yes
- Fibre optic elements: No
- REACH Date: 2023-01-23
- GWP-tot (A1-A3): 12,6937 kgCO2e/M
- REACH Information obligation: No