Feedback
AhlsellProductsElectricAutomation 29-4538 Sensors, machine safetySurveillance relays, pressure guardsVoltage/current monitoring





Carlo Gavazzi
Voltage measurement relay 3-phase for over and under voltage
VOLTAGE LEVEL RELAY DPB01CM48
Article number: Suppl. article no:
3864692
DPB01CM48
to see price and stock
3-phase monitoring relays for phase sequence/Phase break and Over-/Under Voltage for mounting on DIN rails or 11-pin base.
Functional description
The relay is pulled when the phases or the phases + 0 are within the set limits, the relay falls if the limit values are passed after the set time delay (0.1-30s). The relay also monitors phase breaks and phase sequence, at the wrong phase sequence or phase break the relay falls without time delay.
All relevant data, as well as the circuit diagram are clearly marked on the side of the relays.3 LEDs. Green lights up when the control voltage is connected. Yellow lights up when the relay is on and Red flashes during the time, and is lit with a steady light in alarm.
Functional description
The relay is pulled when the phases or the phases + 0 are within the set limits, the relay falls if the limit values are passed after the set time delay (0.1-30s). The relay also monitors phase breaks and phase sequence, at the wrong phase sequence or phase break the relay falls without time delay.
All relevant data, as well as the circuit diagram are clearly marked on the side of the relays.3 LEDs. Green lights up when the control voltage is connected. Yellow lights up when the relay is on and Red flashes during the time, and is lit with a steady light in alarm.
- Article number: 3864692
- Suppl. article no: DPB01CM48
- Ean no: 8030956000214
- Material class QP581B
Technical data
- Type: DPB01CM48
- Design: DIN rail
- Type of electric connection: Screw connection
- With detachable clamps: No
- Rated control supply voltage DC: 0 V
- Phase sequence monitoring: Yes
- Voltage type for actuating: AC
- Phase failure detection: Yes
- Function under voltage detection: Yes
- Function overvoltage detection: Yes
- Phase imbalance monitoring: No
- Voltage measuring range: 323-550 V
- Min. adjustable delay-on energization time: 0.5 s
- Max. permitted delay-on energization time: 6.5 s
- Min. adjustable off-delay time: 0.1 s
- Max. permitted off-delay time: 30 s
- Number of contacts as normally closed contact: 0
- Number of contacts as normally open contact: 0
- Number of contacts as change-over contact: 1
- Width: 22.85 mm
- Height: 83.5 mm
- Depth: 99.5 mm
- Rated control supply voltage AC 60 Hz: 323-550 V
- Rated control supply voltage AC 50 Hz: 323-550 V