Feedback

Motor starter protector switch GV2RT - MOTOR CIRCUIT BREAKER GV2RT16
Schneider Electric

Motor starter protector switch GV2RT

MOTOR CIRCUIT BREAKER GV2RT16
Article number: 
3116671
Suppl. article no: 
GV2RT16





 to see price and stock
Denna produkt innehåller ett eller flera ämnen på kandidatförteckningen.
Motor protection switch with thermal-magnetic protection for motors with high voltage spike at starting, for 3-phase transformers primary side. The magnetic short circuit protection has a fixed trigger level that is approximately 20 times the maximum adjustable value for the thermal protection.
  • Article number: 
    3116671
  • Suppl. article no: 
    GV2RT16
  • Ean no: 
    3389110520699
  • Material class 
    QO021B
Technical data
  • Type: GV2RT16
  • Overload release current setting: 9-14 A
  • Adjustment range undelayed short-circuit release: 280 A
  • Rated short-circuit breaking capacity Icu at 400 V, AC: 15 kA
  • Switch off technique: Thermomagnetic
  • Rated operating voltage: 690 V
  • Rated operation power at AC-3, 400 V: 5.5 kW
  • Rated permanent current Iu: 14 A
  • Phase failure sensitive: Yes
  • Number of poles: 3
  • Device construction: Complete device in housing
  • With integrated auxiliary switch: No
  • With integrated under voltage release: No
  • Rated operation power at AC-3, 230 V: 3 kW
  • Power loss: 2.5 W
  • Degree of protection (IP): IP20
  • Type of electrical connection of main circuit: Screw connection
  • With thermal overload protection: Yes
  • Type of control element: Rocker lever
  • Width: 45 mm
  • Depth: 78.5 mm
  • Height: 89 mm
  • REACH Date: 2025-07-18
  • REACH contains candidate substances: Bly
  • Tripping current magnetic: 280 A
  • REACH Information obligation: Yes