Feedback

Motor starter protector switch GV2P - OR CIRCUIT BREAKER GV2P16
https://www.youtube.com/watch?v=/external-assets/JPEGlarge800_800/44/60/ProductImage78424460.jpg
https://www.youtube.com/watch?v=/external-assets/JPEGlarge800_800/44/61/ProductImage78424461.jpg
https://www.youtube.com/watch?v=/external-assets/JPEGlarge800_800/44/62/ProductImage78424462.jpg
Schneider Electric

Motor starter protector switch GV2P

OR CIRCUIT BREAKER GV2P16
Article number: 
3116060
Suppl. article no: 
GV2P16





 to see price and stock
Denna produkt innehåller ett eller flera ämnen på kandidatförteckningen.
With thermo-magnetic release. Fitted with phase-error protection.
If the short-circuit current does not exceed the switching capacity, a fuse is not required.
Quick fixing for mounting on a DIN-rail or in cladding. Placement independent.
  • Article number: 
    3116060
  • Suppl. article no: 
    GV2P16
  • Ean no: 
    3389110213508
  • Material class 
    QO021B
Technical data
  • Packagin Size: 1 ST/20 ST/320 ST
  • Type: GV2P16
  • Overload release current setting: 9-14 A
  • Adjustment range undelayed short-circuit release: 170 A
  • Rated short-circuit breaking capacity Icu at 400 V, AC: 100 kA
  • Switch off technique: Thermomagnetic
  • Rated operating voltage: 690 V
  • Rated operation power at AC-3, 400 V: 5.5 kW
  • Rated permanent current Iu: 14 A
  • Phase failure sensitive: Yes
  • Number of poles: 3
  • Device construction: Complete device in housing
  • With integrated auxiliary switch: No
  • With integrated under voltage release: No
  • Rated operation power at AC-3, 230 V: 3 kW
  • Power loss: 2.5 W
  • Degree of protection (IP): IP20
  • Type of electrical connection of main circuit: Screw connection
  • With thermal overload protection: Yes
  • Type of control element: Turn button
  • Width: 44.5 mm
  • Depth: 97 mm
  • Height: 89 mm
  • REACH Date: 2025-07-18
  • REACH contains candidate substances: Bly
  • REACH Information obligation: Yes