Feedback

Installation cable fire-resistant Novosafe 450/750 V, Rutab - S-FE-180/PH90 2X1.5 (*5)
Rutab

Installation cable fire-resistant Novosafe 450/750 V, Rutab

S-FE-180/PH90 2X1.5 (*5)
Article number: 
0477000
Suppl. article no: 
0477000





 to see price and stock
Produkten är bedömd hos Byggvarubedömningen med totalbedömningen Accepteras.
Fire-resistant, halogen-free installation cable is intended for fixed installation with high fire safety requirements. Suitable for installation in public buildings such as schools, hospitals, shops, etc. In the event of fire, the cable maintains its electrical function for at least 90 minutes (PH90). Complies with flame-spread class IEC 60332-3-22 (F4A). Halogen-free IEC 60754-2, Flame-proof IEC 60332-1. Low smoke development IEC 61034-2. Fire-proof IEC 60331-11,-21,-23, PH 90 (90 min, 830°C).
Technical data:
Cable type: Novosafe S-FE-180/PH90
Operating voltage: 450/750V
Line construction: Single-wired blank copper cl.1
Line insulation: Cermaic silicon rubber
Outer jacket: Halogen-free special mixture, Orange.
Temperature range: -40°C - +80 °C
Lowest installation temperature: -10° C
Flammability class: IEC 60332-3-22 (F4A)
  • Article number: 
    0477000
  • Suppl. article no: 
    0477000
  • Material class 
    QA820A
Technical data
  • Cable type: NOVOSAFE S-FE
  • Dimension conductor x area: 2x1.5 mm²
  • Colour outer sheath: Orange
  • Outer diameter approximate: 8.1 mm
  • Weight/100 m: 7.8 kg
  • Nominal voltage U0: 450 V
  • Nominal voltage U: 750 V
  • Max. permitted conductor temperature: 90 °C
  • Conductor category: Class 1 = solid
  • Conductor material: Copper
  • Material outer sheath: Polyolefin
  • Core identification: Colour
  • Conductor surface: Bare
  • Flame retardant according to IEC 60332-3-24 (Cat C): Yes
  • Halogen free according to EN IEC 60754-1: Yes
  • Halogen free according to EN IEC 60754-2: Yes
  • Low smoke according to EN IEC 61034-2: Yes
  • Number of cores: 2
  • Nominal cross section conductor: 1.5 mm²
  • REACH Date: 2021-11-24
  • REACH Information obligation: No
  • Insulation integrity: PH 90